Reference sheets · 39 rows · portrait

AWG wire gauge chart

American Wire Gauge from the zero series down: conductor diameter, cross-sectional area, resistance per kilometre, and the indicative chart currents — printed as not defined for the gauges the table does not publish them for.

AWG wire gauge chart

39 rows · EngiRef · sample of the first 8 rows

AWG wire gauge chart. American Wire Gauge from the zero series down: conductor diameter, cross-sectional area, resistance per kilometre, and the indicative chart currents — printed as not defined for the gauges the table does not publish them for.
AWGDiameter
mm
Area
mm²
Resistance
Ω/km
Chassis
A
Transmission
A
000011.684107.220.1608302195
00010.40585.010.2028239165
009.26667.430.2557190145
08.25153.490.3224150125
17.34842.410.4066119110
26.54433.620.51279495
35.82726.670.64657585
45.18921.150.81526070

Diameters follow d = 0.127 × 92^((36−n)/39) mm. The two current columns are INDICATIVE chart values only — they are not NEC 310.16 ampacities and carry no conductor temperature rating, insulation type, ambient correction or bundling adjustment.

  1. The AWG table publishes no indicative current for this gauge. The current columns are chart values only, not NEC 310.16 ampacities: size conductors from NEC 310.16 or your local code with the applicable temperature, ambient and bundling factors, never from this sheet.

Reference values are provided for study and quick reference. Verify against current standards and manufacturer data before safety-critical design.

Every figure on this sheet is also free to read on its own reference page — browse the free reference. Premium pays for the format, not the facts.